Resources
Automation and Control Essential Catalog
Download Now |
Resources
Automation and Control Essential Catalog
Download Now |
device short name | ATV310 |
---|---|
IP degree of protection | IP20 without blanking plate on upper part, IP41 top |
motor power kW | 4 kW |
network number of phases | three phase |
operating position | vertical +/- 10 degree |
output voltage | 380...460 V three phase |
power dissipation in W | 102.72 W at In |
product destination | asynchronous motors |
product or component type | variable speed drive |
product specific application | simple machine |
range of product | Easy Altivar 310 |
[Us] rated supply voltage | 380...460 V - 15...10 % |
acceleration and deceleration ramps | S, linear from 0...999.9 s |
ambient air temperature for operation | -10-55 °C without derating, 55-60 °C protective cover from the top of the drive removed with current derating 2.2 % per °C |
ambient air temperature for storage | -25-70 °C |
analogue input number | 1 |
analogue input type | configurable current AI1 0...20 mA 250 Ohm, configurable voltage AI1 0...10 V 30 kOhm, configurable voltage AI1 0...5 V 30 kOhm |
analogue output number | 1 |
analogue output type | AO1 software-configurable voltage: 0...10 V, impedance: 470 Ohm, resolution 8 bits, AO1 software-configurable current: 0...20 mA, impedance: 800 Ohm, resolution 8 bits |
apparent power | 9.1 kVA |
assembly style | with heat sink |
asynchronous motor control profile | quadratic voltage/frequency ratio, sensorless flux vector control, energy saving ratio |
braking to standstill | by DC injection, <30 s |
braking torque | up to 70 % of nominal motor torque without braking resistor, up to 150 % of nominal motor torque with braking resistor at high inertia |
connector type | RJ45 (on front face) for Modbus |
continuous output current | 9.5 A at 4 kHz |
depth | 184 mm |
discrete input logic | negative logic (sink), > 16 V (state 0), < 10 V (state 1), input impedance 3.5 kOhm, positive logic (source), 0...< 5 V (state 0), > 11 V (state 1) |
discrete input number | 4 |
discrete input type | programmable LI1...LI4 24 V 18...30 V |
discrete output type | logic output LO+, LO-, protected relay output R1A, R1B, R1C 1 C/O |
electrical connection | terminal, clamping capacity: 2.5...4 mm² (L1, L2, L3, PA/+, PB, U, V, W) |
electromagnetic compatibility | voltage dips and interruptions immunity test conforming to EN/IEC 61000-4-11, electrical fast transient/burst immunity test - test level: level 4 conforming to EN/IEC 61000-4-4, electrostatic discharge immunity test - test level: level 3 conforming to EN/IEC 61000-4-2, immunity to conducted disturbances - test level: level 3 conforming to EN/IEC 61000-4-6, radiated radio-frequency electromagnetic field immunity test - test level: level 3 conforming to EN/IEC 61000-4-3, surge immunity test - test level: level 3 conforming to EN/IEC 61000-4-5 |
EMC filter | without EMC filter |
environmental characteristic | chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3, dust pollution resistance class 3S2 conforming to EN/IEC 60721-3-3 |
frequency resolution | display unit: 0.1 Hz, analog input: converter A/D, 10 bits |
height | 151 mm |
insulation | electrical between power and control |
line current | 11.4 A |
linearity error | +/- 0.3 % of maximum value for analogue input |
maximum switching current | 2 A at 250 V AC on inductive load cos phi = 0.4 L/R = 7 ms for logic relay |
maximum transient current | 14.3 A for 60 s |
minimum switching current | 5 mA at 24 V DC for logic relay |
motor power hp | 5.5 hp |
motor slip compensation | adjustable |
net weight | 1.8 kg |
noise level | 50 dB |
nominal switching frequency | 4 kHz |
number of addresses | 1-247 for Modbus |
physical interface | 2-wire RS 485 for Modbus |
pollution degree | 2 conforming to EN/IEC 61800-5-1 |
prospective line Isc | 5 kA |
protection type | line supply overvoltage, line supply undervoltage, overcurrent between output phases and earth, overheating protection, short-circuit between motor phases, against input phase loss in three-phase, thermal motor protection via the drive by continuous calculation of I²t |
Quantity per set | set of 1 |
relative humidity | 5-95 % without condensation conforming to IEC 60068-2-3, 5-95 % without dripping water conforming to IEC 60068-2-3 |
sampling duration | 20 ms, tolerance +/- 1 ms for logic input, 10 ms for analogue input |
shock resistance | 15 gn conforming to EN/IEC 60068-2-27 for 11 ms |
speed drive output frequency | 0.5-400 Hz |
speed range | 1-20 |
standards | EN/IEC 61800-3, EN/IEC 61800-5-1 |
supply | internal supply for reference potentiometer: 5 V (4.75-5.25 V)DC, <10 mA with overload and short-circuit protection, internal supply for logic inputs: 24 V (20.4-28.8 V)DC, <100 mA with overload and short-circuit protection |
supply frequency | 50/60 Hz +/- 5 % |
switching frequency | 2...12 kHz adjustable |
tightening torque | 1.2-1.4 N.m |
time constant | 20 ms +/- 1 ms for reference change |
transient overtorque | 170-200 % of nominal motor torque depending on drive rating and type of motor |
transmission frame | RTU for Modbus |
transmission rate | 4800 bit/s, 9600 bit/s, 19200 bit/s, 38400 bit/s |
type of cooling | integrated fan |
width | 140 mm |